Combined footing

Design a combined footing supporting one exterior and one interior column.

An exterior column, 600 mm x 450 mm, with service loads of 760 kN (dead) and 580 kN (imposed) and an interior column, 600 mm x 600 mm, with service loads of 1110 kN (dead) and 890 kN (imposed) are to be supported on a rectangular footing that cannot protrude beyond the outer face of the exterior column. The columns are spaced at 5.5 m centres and positioned as shown in Figure 7.2.

The allowable bearing pressure is 175 kN/m2, and because of site constraints, the depth of the footing is limited to 750 mm.

Combined Footing Design
Figure 7.2 Plan of combined footing

7.1.2.1 Base size

Column A: 1340 kN and Column B: 2000 kN Distance to centroid of loads from LH end

2000 x 5.5 3340

For uniform distribution of load under base Length of base = 2 x 3.593 say 7.2 m With 750 mm deep base, resultant bearing pressure = 175 - 0.75 x 24 = 157 kN/m2

Was this article helpful?

+4 -1

Responses

  • max
    How design isolated footing eurocode?
    7 years ago
  • Arabella
    When they say a combined footing?
    2 years ago

Post a comment