32.1 x 106

bd2f. 1000 x 1752 x 30

bdf.

0.042 x 1000 x 175 x 30 460

Use T16 @ 300 mm crs. (670 mm2/m) top and bottom outside 600 mm wide moment transfer zone and over area determined in punching calculation

The division of panels into column and middle strips is shown in Figure 4.17. BS 8110

Figure 3.12

Although BS 8110 indicates a 2.36 m wide column strip at column B2, a 2.6 m width has been used in the following calculations. This is considered reasonable as a loaded width of 5.2 m has been taken in the analysis for grid B and grid 2.